LuxConnect
ICT Campus Bettembourg DC 1.1
TECHNICAL INFORMATION
- Operational since: June 2009
- Power available: 2 x 6,3 MVA
- Power loads: Up to 5 kW/rack
- Floor load: 1.500 kg/m2
- UPS systems: Redundant 2 x (N+1)
- Generator autonomy: 48 hours; 24/365 refuel contracts
- Cooling redundancy: 2 x N
- Cooling specifications: Water input 10°C; output 15°C
- Gross size: 10.000 m2
- IT room height: 3,80 m
- Raised floor: 1,00 m
- Equipment elevator: 4.000 kg
- Power to IT rooms: Average 1.150 W/m2
- Server room temperature: 18-27°C – ASHRAE TC9.9 Class A1 recommended
- Net size: 3.100 m2
- PUE: 1,45 / 1,5
- SLA: 99,995%
Technical highlights
- 100% renewable energy sources
- Electromagnetic protection concept
- Remote central monitoring of all technical systems
- Carrier neutral
- International & national telecom operators
Internet Exchanges
- NL-ix
- LU-CIX
Security & Access
- Fire and very early smoke detection
- Neutral gas (nitrogen) fire suppression system
- Water leakage detection
- Intrusion detection
- 24/7/365 on site security guards with controlled access
CARRIERS
- BICS
- British Telecom
- cegecom
- CETREL
- Cogent
- Colt
- Datacenter.eu
- Destiny
- inexio
- IX Reach
- Join
- KPN international
- Level 3
- LuxConnect
- Luxembourg Online
- MTX Connect
- NL-ix
- NTT Communications
- Orange Luxembourg
- POST Telecom
- Foundation RESTENA
- root
- Tango
- Telecom Luxembourg
- Telefonica
- TeliaSonera IC
- Telindus Telecom
Street Address: 202, Z.A.E. Wolser F, L-3290 Bettembourg
GPS Localisation: CR161a L-3235 Bettembourg
Interested in being hosted in DC 1.1?