EBRC
Resilience Centre Luxembourg East
TECHNICAL INFORMATION
- Operational since: 2012
- Design: 2N
- Power available: max. 6,4 MW UPS
- Floor load: 2.000 kg/m²
- UPS systems: Dynamic UPS Systems
- Generator autonomy: 65 hours
- Cooling redundancy: 2N
- IT room height: 3,50 m
- Raised floor: 1 m
- Equipment elevator: 1 lift and 1 goods elevator + loading docks
- Power to IT rooms: IT suites can be energy-fuelled up to 2.000 W/m² depending on the configuration
- Server room temperature: : ≤ 22°C (inlet air for servers)
- Net IT surface: 5.000 m²
- SLA: 99,995% guaranteed